EasyManua.ls Logo

Siemens SIMATIC ET 200SP - Page 208

Siemens SIMATIC ET 200SP
270 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
User data variants
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Manual, 07/2018, A5E42674880-AA
207
Active power L1L2L3 (ID 253 or FD
H
)
Table D- 3 Active power L1L2L3
Byte
Allocation
Data
type
Unit
Value range
Meas-
ured
value
ID
0
User data variant
BYTE
-
253 (FD
H
)
-
1 Quality information = QQ
1
I
3
U
3
I
2
U
2
I
1
U
1
BYTE Bit string qq xx xx xx -
2 ... 3
Current L1
UINT
1 mA
0 … 65535
66007
4 ... 5
Current L2
UINT
1 mA
0 … 65535
66008
6 ... 7
Current L3
UINT
1 mA
0 … 65535
66009
8 ... 9
Active power L1
INT
1 W
-27648 … 27648
66013
10 ... 11
Active power L2
INT
1 W
-27648 … 27648
66014
12 ... 13
Active power L3
INT
1 W
-27648 … 27648
66015
14 ... 15
Total active power L1L2L3
INT
1 W
-27648 … 27648
66034
16 ... 19 Total active energy L1L2L3 DINT 1 Wh -2147483647...
+2147483647
225
20
Power factor L1
USINT
0.01
0 … 100
66019
21
Power factor L2
USINT
0.01
0 … 100
66020
22
Power factor L3
USINT
0.01
0 … 100
66021
23
Total power factor L1L2L3
USINT
0.01
0 … 100
66037
24
Scaling current L1
USINT
-
0 ... 255
-
25
Scaling current L2
USINT
-
0 ... 255
-
26
Scaling current L3
USINT
-
0 ... 255
-
27
Scaling active power L1
USINT
-
0 ... 255
-
28
Scaling active power L2
USINT
-
0 ... 255
-
29
Scaling active power L3
USINT
-
0 ... 255
-
30
Scaling active power L1L2L3
USINT
-
0 ... 255
-
31
Scaling total active energy L1L2L3
USINT
-
0 ... 255
-

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP

Related product manuals