User data variants
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Manual, 07/2018, A5E42674880-AA
209
Apparent power L1L2L3 (ID 251 or FB
H
)
Table D- 5 Apparent power L1L2L3
Byte
Allocation
Data
type
Unit
Value range
Meas-
ured
value
ID
0
User data variant
BYTE
-
251 (FB
H
)
-
1 Quality information = QQ
1
I
3
U
3
I
2
U
2
I
1
U
1
BYTE Bit string qq xx xx xx -
2 ... 3
Current L1
UINT
1 mA
0 … 65535
66007
4 ... 5
Current L2
UINT
1 mA
0 … 65535
66008
6 ... 7
Current L3
UINT
1 mA
0 … 65535
66009
8 ... 9
Apparent power L1
INT
1 VA
-27648 … 27648
66010
10 ... 11
Apparent power L2
INT
1 VA
-27648 … 27648
66011
12 ... 13
Apparent power L3
INT
1 VA
-27648 … 27648
66012
14 ... 15
Total apparent power L1L2L3
INT
1 VA
-27648 … 27648
66036
16 ... 19
Total apparent energy L1L2L3
DINT
1 VAh
0 to 2147483647
224
20
Power factor L1
USINT
0.01
0 … 100
66019
21
Power factor L2
USINT
0.01
0 … 100
66020
22
Power factor L3
USINT
0.01
0 … 100
66021
23
Total power factor L1L2L3
USINT
0.01
0 … 100
66037
24
Scaling current L1
USINT
-
0 ... 255
-
25
Scaling current L2
USINT
-
0 ... 255
-
26
Scaling current L3
USINT
-
0 ... 255
-
27
Scaling apparent power L1
USINT
-
0 ... 255
-
28
Scaling apparent power L2
USINT
-
0 ... 255
-
29
Scaling apparent power L3
USINT
-
0 ... 255
-
30 Scaling apparent power L1L2L3 USINT - 0 ... 255 -
31
Scaling total apparent energy L1L2L3
USINT
-
0 ... 255
-

Table of Contents