User data variants
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Manual, 07/2018, A5E42674880-AA
211
Total energy L1L2L3 (ID 249 or F9
H
)
Table D- 7 Total energy L1L2L3
Byte
Allocation
Data
type
Unit
Value range
Meas-
ured
value
ID
0
User data variant
BYTE
-
249 (F9
H
)
-
1 Quality information = QQ
1
I
3
U
3
I
2
U
2
I
1
U
1
BYTE Bit
string
qq xx xx xx -
2
Reserved
BYTE
-
-
-
3 Reserved BYTE - - -
4 ... 7
Total active energy inflow L1L2L3
UDINT
1 Wh
0 to 2147483647
210
8 ... 11
Total active energy outflow L1L2L3
UDINT
1 Wh
0 to 2147483647
211
11 ... 15
Total reactive energy inflow L1L2L3
UDINT
1 varh
0 to 2147483647
212
16 ... 19
Total reactive energy outflow L1L2L3
UDINT
1 varh
0 to 2147483647
213
20 ... 23
Total apparent energy L1L2L3
UDINT
1 VAh
0 to 2147483647
214
24
Reserved
BYTE
-
-
-
25
Scaling active energy, inflow
USINT
-
0 ... 255
-
26
Scaling active energy, outflow
USINT
-
0 ... 255
-
27
Scaling reactive energy, inflow
USINT
-
0 ... 255
-
28
Scaling reactive energy, outflow
USINT
-
0 ... 255
-
29
Scaling apparent energy
USINT
-
0 ... 255
-
30
Reserved
BYTE
-
-
-
31
Total power factor L1L2L3
USINT
0.01
0 … 100
66037