User data variants
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
214 Manual, 07/2018, A5E42674880-AA
Energy L3 (ID 246 or F6
H
)
Table D- 10 Energy L3
Byte
Allocation
Data
type
Unit
Value range
Meas-
ured
value
ID
0
User data variant
BYTE
-
246 (F6
H
)
-
1 Quality information = QQ
1
I
3
U
3
I
2
U
2
I
1
U
1
BYTE Bit
string
qq xx xx xx -
2 ... 3
Current L3
UINT
1 mA
0 … 65535
66009
4 ... 7 Active energy inflow L3 UDINT 1 Wh 0 to 2147483647 62310
8 ... 11
Active energy L3, outflow
UDINT
1 Wh
0 to 2147483647
62311
11 ... 15
Reactive energy inflow L3
UDINT
1 varh
0 to 2147483647
62312
16 ... 19
Reactive energy outflow L3
UDINT
1 varh
0 to 2147483647
62313
20 ... 23
Apparent energy L3
UDINT
1 VAh
0 to 2147483647
62314
24
Scaling current L3
USINT
-
0 ... 255
-
25
Scaling active energy inflow L3
USINT
-
0 ... 255
-
26
Scaling active energy outflow L3
USINT
-
0 ... 255
-
27
Scaling reactive energy inflow L3
USINT
-
0 ... 255
-
28
Scaling reactive energy outflow L3
USINT
-
0 ... 255
-
29
Scaling apparent energy L3
USINT
-
0 ... 255
-
30
Reserved
BYTE
-
-
-
31
Power factor L3
USINT
0.01
0 … 100
66021
Basic variables three-phase measurements (ID 245 or F5
H
)
Table D- 11 Basic variables three-phase measurements
Byte
Allocation
Data
type
Unit
Value range
Meas-
ured
value
ID
0
User data variant
BYTE
-
245 (F5
H
)
-
1 Quality information = QQ
1
I
3
U
3
I
2
U
2
I
1
U
1
BYTE Bit
string
qq xx xx xx -
2 ... 5 Total active power L1L2L3 REAL 1 W -3 x 10
9
... +3 x 10
9
34
6 ... 9
Total active energy outflow L1L2L3
REAL
1 Wh
0.0 ... 3.4 x 10
38
62418
10 ... 13
Total active energy inflow L1L2L3
REAL
1 Wh
0.0 ... 3.4 x 10
38
62417
14 ... 17
Current L1
REAL
1 A
0.0 … 100000.0
7
18 ... 21
Current L2
REAL
1 A
0.0 … 100000.0
8
22 ... 25
Current L3
REAL
1 A
0.0 … 100000.0
9
26 ... 27 Voltage UL1-N UINT 0.01 V 0 … 65535 66001
28 ... 29
Voltage UL2-N
UINT
0.01 V
0 … 65535
66002
30 ... 31
Voltage UL3-N
UINT
0.01 V
0 … 65535
66003

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200SP and is the answer not in the manual?

Siemens SIMATIC ET 200SP Specifications

General IconGeneral
System TypeDistributed I/O System
MountingDIN Rail
Communication ProtocolPROFINET, PROFIBUS
IP RatingIP20
CategoryI/O Systems
Supply Voltage24 V DC
ModularityYes
Hot SwappingYes
Storage Temperature-40°C to +70°C
Digital InputsYes
Digital OutputsYes
Analog InputsYes
Analog OutputsYes
Communication InterfacePROFINET, PROFIBUS
Number of ModulesUp to 64
Relative Humidity5 to 95% (non-condensing)
Operating Temperature-25°C to +60°C