User data variants
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Manual, 07/2018, A5E42674880-AA
213
Energy L2 (ID 247 or F7
H
)
Table D- 9 Energy L2
Byte
Allocation
Data
type
Unit
Value range
Meas-
ured
value
ID
0
User data variant
BYTE
-
247 (F7
H
)
-
1 Quality information = QQ
1
I
3
U
3
I
2
U
2
I
1
U
1
BYTE Bit
string
qq xx xx xx -
2 ... 3
Current L2
UINT
1 mA
0 … 65535
66008
4 ... 7 Active energy inflow L2 UDINT 1 Wh 0 to 2147483647 62210
8 ... 11
Active energy outflow L2
UDINT
1 Wh
0 to 2147483647
62211
11 ... 15
Reactive energy inflow L2
UDINT
1 varh
0 to 2147483647
62212
16 ... 19
Reactive energy outflow L2
UDINT
1 varh
0 to 2147483647
62213
20 ... 23
Apparent energy L2
UDINT
1 VAh
0 to 2147483647
62214
24
Scaling current L2
USINT
-
0 ... 255
-
25
Scaling active energy inflow L2
USINT
-
0 ... 255
-
26
Scaling active energy outflow L2
USINT
-
0 ... 255
-
27
Scaling reactive energy inflow L2
USINT
-
0 ... 255
-
28
Scaling reactive energy outflow L2
USINT
-
0 ... 255
-
29
Scaling apparent energy L2
USINT
-
0 ... 255
-
30
Reserved
BYTE
-
-
-
31
Power factor L2
USINT
0.01
0 … 100
66020

Table of Contents