User data variants
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
Manual, 07/2018, A5E42674880-AA
219
Basic variables measurement data profile (ID 226 or E2
H
)
Table D- 16 Basic variables measurement data profile Energy E2
Byte
Allocation
Data
type
Unit
Value range
Meas-
ured
value
ID
0
User data variant
BYTE
-
226 (E2
H
)
-
1 Quality information = QQ
1
I
3
U
3
I
2
U
2
I
1
U
1
BYTE Bit
string
qq xx xx xx -
2 ... 5 Total active power L1L2L3 REAL 1 W -3.0 x 10
9
... + 3.0
x 10
9
34
6 ... 9
Total active energy inflow L1L2L3
REAL
1 W
3.0 x 10
9
200
10 ...13
Total active energy outflow L1L2L3
REAL
1 W
3.0 x 10
9
201
Basic variables measurement data profile (ID 225 or E1
H
)
Table D- 17 Basic variables measurement data profile Energy E1
Byte
Allocation
Data
type
Unit
Value range
Meas-
ured
value
ID
0
User data variant
BYTE
-
225 (E1
H
)
-
1 Quality information = QQ
1
I
3
U
3
I
2
U
2
I
1
U
1
BYTE Bit
string
qq xx xx xx -
2 ... 5 Total active power L1L2L3 REAL 1 W -3.0 x 10
9
... + 3.0
x 10
9
34
Basic variables measurement data profile (ID 224 or E0
H
)
Table D- 18 Basic variables measurement data profile Energy E0
Byte
Allocation
Data
type
Unit
Value range
Meas-
ured
value
ID
0
User data variant
BYTE
-
224 (E0
H
)
-
1 Quality information = QQ
1
I
3
U
3
I
2
U
2
I
1
U
1
BYTE Bit
string
qq xx xx xx -
2 ... 5
Current L1
REAL
1 A
0.0 … 100000.0
7
6 ... 9
Current L2
REAL
1 A
0.0 … 100000.0
8
10 ...13
Current L3
REAL
1 A
0.0 … 100000.0
9

Table of Contents