Reading and processing measured values
6.1 Basics for reading measured values
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
42 Manual, 07/2018, A5E42674880-AA
Initial module startup
After the first startup or restart of the module, the parameters are transferred to the module.
You can preset a user data variant in the parameters of the hardware configuration. This
remains in effect until a different user data variant is selected in the output data (byte 0). This
allows input user data to be modified dynamically according to the requirements of the
process.
The user data variant defined in parameter data record 128 or configuration tool is used
under the following conditions:
A "0" is written in byte 0 in the output data of a user data variant.
Byte 0 in the output data of a user data variant contains an invalid value:
Coding of the user data variant not available, or
Available address space is not sufficient for the selected user data variant.
See "Selecting the module versions (Page 32)".
Current measured values become "0"
The current and all other measured values based on it are suppressed (or set to "0") in the
data records and in the user data in the following cases:
The fed-in current of the current transformer is less than the configured "Low limit for
measuring current in relation to nominal value current [0.1%]" parameter.
Fed-in secondary current at the channel is higher than 12 A.
Among others, the following measured values and derived measured variables of the phase
involved become "0":
Effective current value
Active power
Reactive power
Apparent power
Phase angle
Power factor
A floating mean value is formed from the power values. These only become "0" after a
corresponding time. The operating hours counter and the energy counter for active, reactive
and apparent energy of the reset phase stops counting.

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200SP and is the answer not in the manual?

Siemens SIMATIC ET 200SP Specifications

General IconGeneral
System TypeDistributed I/O System
MountingDIN Rail
Communication ProtocolPROFINET, PROFIBUS
IP RatingIP20
CategoryI/O Systems
Supply Voltage24 V DC
ModularityYes
Hot SwappingYes
Storage Temperature-40°C to +70°C
Digital InputsYes
Digital OutputsYes
Analog InputsYes
Analog OutputsYes
Communication InterfacePROFINET, PROFIBUS
Number of ModulesUp to 64
Relative Humidity5 to 95% (non-condensing)
Operating Temperature-25°C to +60°C

Related product manuals