EasyManua.ls Logo

Siemens SIMATIC ET 200SP - Page 65

Siemens SIMATIC ET 200SP
270 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Energy counters
7.3 Starting and and stopping energy meters
Analog input module AI Energy Meter 480VAC/CT HF (6ES7134-6PA00-0CU0)
64 Manual, 07/2018, A5E42674880-AA
Counting with gate
Requirements:
The current value is higher than the configured "Low limit for measuring current in relation to
nominal value current [0.1%]".
Procedure
If you wish to start counting using the gate, proceed as follows:
1. Activate the parameter "Enable energy meter gate" in the parameter assignment of the
module.
2. Set the DQ bit for the counter gate (Bit 6) in control byte 1 in the output data.
The module starts counting as soon as there is an edge change from 0 -> 1 at the DQ bit for
the counter gate.
If you wish to stop the counting again, then reset Bit 6 in control byte 1 in the output data.
Counting stops at an edge change from 1 -> 0.
The "Enable gate control for the energy counter" parameter and the DQ bit for the "counter
date" behave like the parallel connection of contacts.
Figure 7-8 Gate enabled

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP

Related product manuals