5.4 How to migrate SQL Server 2000 databases
WinCC projects that were created with versions prior to WinCC V6.2 SP2 include database
settings of the SQL Server 2000.
To access databases with SQL Server 2014 that were created with versions prior to SQL
Server 2005, you must change the compatibility setting.
To do so, use the SQL Server Management Studio up to maximum SQL Server 2008. You
connect
the
database using the *.MDF file, change the settings and remove the database once
again.
Edit all databases that are part of your WinCC project:
Databases in the local WinCC project
Distributed systems: Databases on all PCs of the WinCC system
Databases on the file server
Databases on an archive server
Swapped-out databases
Requirement
You have created backup copies of the databases in the WinCC system.
Back up the associated *.LDF file for each *.MDF file.
The SQL Server up to version SQL Server 2008 is installed on the PC.
Procedure
1. Open the SQL Server Management Studio.
2. Connect to the WinCC instance. Enter the following path in the "Server name" field:
<Computer name>\WINCC
3. Select the entry "Append" in the shortcut menu of "Databases".
The "Append databases" dialog opens.
4. Click "Add".
The "Search database files" dialog opens.
5. Select the project database and confirm with "OK".
6. Select the item "Properties" in the shortcut menu of the database.
The "Database Properties" dialog opens.
In the "Options" view, the field "Degree of compatibility" has the entry "SQL Server 2000
(80)".
7. In the "Degree of compatibility" drop down list under "Options" select the entry "SQL Server
2008 (100)". Confirm your entries with "OK".
8. Select the item "Tasks > Disconnect" in the shortcut menu of the database.
The "Disconnect database" dialog opens.
Migration
5.4 How to migrate SQL Server 2000 databases
WinCC: General information and installation
142 System Manual, 02/2017, A5E40840020-AA

Table of Contents

Other manuals for Siemens SIMATIC HMI series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC HMI series and is the answer not in the manual?

Siemens SIMATIC HMI series Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC HMI series
CategoryControl Panel
LanguageEnglish

Related product manuals