2.2.2 Defining Access Rights in the Operating System
Introduction
To support you in protecting your system, WinCC offers a structured user management:
Protect your system against unauthorized access.
Assign each user the required rights.
In order to work with WinCC, certain folders can be enabled for access via the network. For
security reasons, you should only assign access rights to these folders to authorized users.
You manage access rights via the Windows Standard user groups and user groups created
by WinCC.
Access rights specified in WinCC
Following WinCC installation, WinCC automatically establishes the following local groups in
Windows User and Group Administration:
"SIMATIC HMI"
All users must be members of the "SIMATIC HMI" user group. These members may create
local projects, and may process, start, and access these projects remotely. Access to the
WinCC database is limited to the minimum rights necessary (read/write). By default, the
user who carries out the WinCC installation and the local administrator are members of this
group. Additional members must be added manually by an administrator.
"SIMATIC HMI Viewer"
These members have read access only to configuration and runtime data in the WinCC
database. This group is primarily used for accounts for Web publication services, e.g., IIS
(Internet Information Services) account for operation of WinCC WebNavigator.
Access to folder "<Installation Directory>/WinCC/aplib"
Following installation, the directory "Installation Directory/WinCC/aplib" named
"SCRIPTFCT" is unlocked for the "SIMATIC HMI" user group. This directory contains
central libraries for project script functions.
User Groups and User Rights
The following overview contains the tasks of the different user groups with the access rights
and instructions required to assign these access rights.
WinCC Installation
Task: WinCC Installation
Role: Configuration engineer, Administrator
Authorization: Windows Administrator rights
Procedure:
Prior to installation, ensure that you have local administrator rights on the computer.
Explanation:
You need local administrator rights to install WinCC.
WinCC Release Notes
2.2 Notes on operation
WinCC: General information and installation
56 System Manual, 02/2017, A5E40840020-AA

Table of Contents

Other manuals for Siemens SIMATIC HMI series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC HMI series and is the answer not in the manual?

Siemens SIMATIC HMI series Specifications

General IconGeneral
SeriesSIMATIC HMI
CategoryControl Panel
Display TypeTFT LCD
Touch ScreenYes (resistive or capacitive, depending on model)
ProcessorVaries by model (e.g., ARM-based processors)
StorageVaries by model (e.g., Flash memory, microSD card slot)
Communication InterfacesEthernet, USB
Protection ClassIP65 (front panel), depending on model
Operating Temperature0 to 50°C, -20 to 60°C
Power Supply24 V DC
Memory128 MB, 256 MB