Number Type Short description
in Alarm Logging
Text in diagnosis Description
1007005 3 Action error 2 Fault in LoadFunktion
new_function error:
"new_function": doubly de‐
fined function
Two *.fct files are using the same func‐
tion name in the directory "<Project>
\Library".
Measures:
When executing menu command "Re‐
generate header" in the Global Script,
you are notified of the duplicate file
name.
1007005 3 Action error 2 10 errors occurs, no more er‐
rors will be reported
One of the above faults has occurred
10 times and will no longer be logged
for performance reasons.
1007006 3 Tag error Variable %s not exist Requested tag does not exist.
1007006 3 Tag error Variable %s timeout Tag request was not answered within
a certain amount of time.
1007006 2 Tag error 10 errors occurs, no more er‐
rors will be reported
One of the above faults has occurred
10 times and will no longer be logged
for performance reasons.
1007007 1 Info FindFirstFile INVALID_HAN‐
DLE_VALUE GetLastError()
%d
On multi-user projects, the directory ..
\Siemens\WinCC\aplib
is enabled with
the name SCRIPTFCT.
If there is no access to the directory,
this entry is found and a second at‐
tempt is started.
1007007 1 Info Alles vorbei INVALID_HAN‐
DLE_VALUE GetLastError()
%d
The second access attempt failed. The
SCRIPTFCT directory and the func‐
tions and
header files contained within
are not available.
Possible causes:
Network is faulty, no current Service‐
Pack for NT or changed access author‐
ization.
1007007 1 Info countall %d in szFolder %s Number of functions in one directory.
1007007 1 Info before Read Standardfunc‐
tion
Before reading the standard functions.
1007007 1 Info runtimeproject %s ok(getpro‐
jectdir) %d
Project path definition.
1007007 1 Info global %s szProjectLibDir %s The global path and the project path
are output.
1007007 1 Info count StandardFunctions: %d Number of standard functions.
1007007 1 Info count StandardFunctions
+ProjectFunctions: %d
Number of standard and project func‐
tions.
1007007 1 Info DM_NOTIFY_SHUTDOWN Request, to end runtime.
1007007 1 Info RemoveClient A client has disabled the connection.
1007007 1 Info InstallClient ok Communication Client/Server disa‐
bled.
1007007 1 Info InstallClient no ok A client was not able to establish com‐
munication with the server.
1007007 1 Info no client Client not logged in.
WinCC diagnosis
6.4 Appendix
WinCC: General information and installation
System Manual, 02/2017, A5E40840020-AA 191