Configuration
3.20 Configuring data points
Configuration - DNP3
110 Configuration Manual, 11/2018, C79000-G8976-C508-01
The table lists the supported data point types of the modules with the classifications of the
protocol and the compatible S7 data types of the CPU.
Note
Effect of the change of arrays for data points
If an array is modified later, the d
ata point must be recreated.
Data point types
Table 3- 4 Data point types, DNP3 object groups, variants and compatible S7 data types
Format (memory
requirements)
Data point type
DNP3 object
group
[variation]
Direction
S7 data types
Operand area
CP
TIM
Bit
Binary Input
1 [1, 2]
in
Bool
Bool
I, Q, M, DB
Binary Input Event
2 [1, 2]
in
Bool
Bool
I, Q, M, DB
Binary Output
1)
10 [2]
out
Bool
Bool
Q, M, DB
Binary Output Event
1)
11 [1, 2]
out
Bool
Bool
Q, M, DB
Binary Command
12 [1]
out
Bool
Byte
Q, M, DB
Integer (16 bits)
Counter
20 [2]
in
UInt, Word
Word
I, Q, M, DB
Frozen Counter
2)
21 [2, 6]
in
UInt, Word
Word
I, Q, M, DB
Counter Event
22 [2, 6]
in
UInt, Word
Word
I, Q, M, DB
Frozen Counter
Event
3)
23
[2, 6] in UInt, Word Word I, Q, M, DB
Analog Input
30 [2]
in
Int
Int
I, Q, M, DB
Analog Input Event
32 [2]
in
Int
Int
I, Q, M, DB
Analog Output Sta-
tus
4)
40
[2] out Int Int Q, M, DB
Analog Output
41 [2]
out
Int
Int
Q, M, DB
Analog Output
Event
4)
42
[2, 4] out Int Int Q, M, DB
Integer (32 bits)
Counter
20 [1]
in
DWord
DWord
I, Q, M, DB
Frozen Counter
2)
21 [1, 5]
in
DWord
DWord
I, Q, M, DB
Counter Event
22 [1, 5]
in
DWord
DWord
I, Q, M, DB
Frozen Counter
Event
3)
23
[1, 5] in DWord DWord I, Q, M, DB
Analog Input
30 [1]
in
DInt
-
Q, M, DB
Analog Input Event
32 [1]
in
DInt
-
Q, M, DB
Analog Output Sta-
tus
4)
40
[1, 3] out DInt DWord Q, M, DB
Analog Output
41 [1]
out
DInt
DWord
Q, M, DB
Analog Output
Event
4)
42
[1] out DInt DWord Q, M, DB

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC TeleControl DNP3 and is the answer not in the manual?

Siemens SIMATIC TeleControl DNP3 Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC TeleControl DNP3
CategoryControl Unit
LanguageEnglish

Related product manuals