Configuration
3.20 Configuring data points
Configuration - DNP3
Configuration Manual, 11/2018, C79000-G8976-C508-01
129
Monitors the number of pulses sent by the master (Count). If the number of
pulses receive
d from the master exceeds the value configured here, the
If you enter 0 (zero), the monitoring is disabled.
l-
Monitors the pulse duration transmitted by the master in the command frame
(On
-time).
If the pulse duration exceeds the value configured here, the command is
rejected by the station module, provided no "Pulse duration replacement
time" is configured.
When the "Max. pulse duration" is exceeded
and "Pulse duration replace-
ment time" is configured or when the received pulse duration is 0, the "Pulse
duration replacement time" is used.
Pulse duration replacement time (s)
l-
alue for the pulse duration
The replacement value is used in the following cases:
The pulse duration received from the master exceeds the value
configured under "Max. pulse duration".
The received pulse duration is 0.
If the value is 0 (zero), no replaceme
nt value is used. The command is dis-
If the "Max. pulse duration" and "Pulse duration replacement time" are both
configured with zero, every command is discarded.
Select and Operate / Direct Operate
l-
Execute directly (Direct Operate)
Select and operate (Select and Operate)
Execute directly
The command is immediately transmitted to the CPU of the station for