Configuration
3.20 Configuring data points
Configuration - DNP3
128 Configuration Manual, 11/2018, C79000-G8976-C508-01
No specific parameters are available for the output option LATCH_ON/OFF. The station
module evaluates the control codes of the master station according to the table above.
PULSE_ON parameters
Master
Name:
Number of pulses
Range of va
l-
ues:
1 ... 255
Default:
1
Explanation:
Number of pulses that the data point of the master sends to the correspon
d-
ing data point of the station.
Name:
Puls-Steuerung
Range of va
l-
ues:
NUL
CLOSE
TRIP
Explanation:
Trip
-Close Code for Control Code "PULSE_ON". The data point sends the
configured code to the corresponding data point of the station. See above for
the meaning.
Name:
Pulse ON duration
Range of va
l-
ues:
0 ... 4294967295
Default:
10
Explanation:
Duration (milli
seconds) for "On-time". The data point sends the configured
time to the corresponding data point of the station.
Name:
Pulse OFF duration
Range of va
l-
ues:
0 ... 4294967295
Default:
0
Explanation:
Duration (milliseconds) for "Off
-time". The data point sends the configured
time to the corresponding data point of the station.
Station
Name:
Max. number of pulses
Range of va
l-
ues:
0 ... 255
Default:
1