3 System Messages
285Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
2313 0 OSCOP Fault during change to normal mode by
OSCOP P
Hotline
2314 2 OSCOP Lock mode activated by OSCOP -
2315 0 OSCOP Fault during change to lock mode by
OSCOP P
Hotline
2316 1 OSCOP OSCOP P communication request via V20/
V30 protocol rejected
Make sure to use OSCOP P, version 6.60
or higher and set device type
„SIMEAS R-PMU“.
2561 2 OSCOP Logon service mode Switching from normal mode to service
mode; possible reason: Firmware update
rejected, parameter or password change
rejected
2562 0 OSCOP Unable to logon for service mode Hotline
2563 2 OSCOP Logoff service mode -
2564 1 OSCOP Logoff service mode with device reboot Switching from normal mode to service
mode; possible reason: Deleting fault
records via OSCOP P, firmware update or
parameter changes
2566 1 OSCOP Incorrect password -
3120 2 SYNC External synchronization pulse OK -
3121 2 SYNC Device synchronized -
3122 0 SYNC Synchronization fault: Pulse loss Synchronization signal lost. Check the clock
incl. antenna, antenna cable and the
synchronization signal cable.
3123 1 SYNC Synchronization: Non-critical pulse failure Synchronization signal lost for a short time.
Check the clock incl. antenna, antenna
cable and the synchronization signal cable if
this error occurs repeatedly.
3124 0 SYNC Synchronization fault: Too many non-critical
pulse losses
Synchronization signal lost for a short time
several times. Check the clock incl.
antenna, antenna cable and the
synchronization signal cable.
3125 0 SYNC Synchronization fault: Pulse width invalid Pulse width of the synchronization signal
does not meet the specification. Check
parameterization of clock master.
3126 0 SYNC Synchronization fault: Pulse distance invalid Pulse gap must be 1 s for GPS/DCF77 or
60 s for minute pulse. Check
parameterization of clock master.
3127 0 SYNC Synchronization fault: DCF77 minute mark
not found
No valid DCF77 signal detected. Check
parameterization of clock master.
3128 0 SYNC DCF77 synchronization parity fault: Check clock master and synchronization
signal cable; no valid DCF77 signal
detected.
3129 0 SYNC Synchronization fault: Non-supported Sync-
Box 7KE6000-8H* connected
The Sync-Box is supported as of SIMEAS
R-PMU firmware V40.01.
3184 2 SYSTEM DCF77 synchronization-supported -
3185 1 SYSTEM Synchronization fault: Manual time setting
rejected
Time setting via OSCOP P is not allowed if
SIMEAS R-PMU is synchronized via GPS
signal.
3186 1 SYSTEM Manual time setting rejected, minimum
distance not observed
Time gap between two time setting
commands must be at least 4 hours.
3187 1 SYNC Leap second announcement received -
3188 1 SYNC Leap second -
3189 2 SYNC System time zone changed Device time zone was changed due to a
new parameterization or a firmware
upgrade.
Log No. Type Class Description Comment

Table of Contents

Other manuals for Siemens SIMEAS R

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMEAS R and is the answer not in the manual?

Siemens SIMEAS R Specifications

General IconGeneral
BrandSiemens
ModelSIMEAS R
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals