3 System Messages
284 Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
1824 0 SYSTEM Common alarm A general common alarm occurred.
For further information on this fault, refer to
detailed log entries.
1825 0 SYSTEM CPU fault Several possible reasons: DAU and CPU
software version do not match, firmware
update recommended; CPU hardware error;
contact hotline if necessary
1826 1 SYSTEM Data fault TAR/TPR record cannot be used due to
inconsistent DAU data. Check via external
or manual trigger if recording is now
possible without errors. LED Data fault must
now be off, if not contact hotline.
1827 0 SYSTEM OSCOP P communication aborted. Fault
no.:
Communication is terminated if there is no
user activity for 10 minutes. Otherwise,
check the communication link.
2049 0 DAU Invalid link command requested.
Cmd number:
Hotline, install SIMEAS R-PMU firmware or
OSCOP P update
2050 2 DAU Measurement system time set Measurement system time was set due to
change of RTC time. Message appears on
device start, too.
2051 1 DAU Measurement system time could not be set Hotline
2056 2 DAU Measurement system started Measurement system was started after a
device start or after the termination of the
service mode.
2057 0 DAU Unable to start measurement system Hotline
2058 1 DAU Measurement system stopped Measurement system was stopped when
changing to service mode or due to a
hardware fault.
2059 0 DAU Unable to stop measurement system Hotline
2064 2 DAU Recording initiated by manual trigger -
2065 0 DAU Recording not initiated by manual trigger Hotline
2066 2 DAU Recording initiated by OSCOP P trigger -
2067 0 DAU Recording not initiated by OSCOP P trigger Hotline
2068 2 DAU Recording initiated by external start -
2069 0 DAU Recording not initiated by external start Hotline
2070 2 DAU Recording terminated by external start -
2071 0 DAU Recording not terminated by external start Hotline
2072 2 DAU Recording initiated by network trigger -
2073 0 DAU Recording not terminated by external start Hotline
2074 2 DAU Change to normal mode OK -
2075 0 DAU Fault during change to normal mode Hotline
2076 2 DAU Change to test mode OK -
2077 0 DAU Fault during change to test mode Hotline
2078 2 DAU Change to lock mode OK SIMEAS R-PMU can change to lock mode
automatically or via control panel or via
OSCOP P. Check further log messages for
details.
2079 0 DAU Fault during change to lock mode Hotline
2306 0 OSCOP Login could not be performed Hotline, install SIMEAS R-PMU firmware or
OSCOP P update
2307 2 OSCOP RTC set. New time stamp: RTC was set via OSCOP P.
2310 2 OSCOP Test mode activated by OSCOP P -
2311 0 OSCOP Fault during change to test mode by
OSCOP P
Hotline
2312 2 OSCOP Normal mode activated by OSCOP P -
Log No. Type Class Description Comment

Table of Contents

Other manuals for Siemens SIMEAS R

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMEAS R and is the answer not in the manual?

Siemens SIMEAS R Specifications

General IconGeneral
BrandSiemens
ModelSIMEAS R
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals