3 System Messages
283Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
1282 2 CALL_PC Callback PC was acknowledged by
OSCOP P. Interface:
-
1283 1 CALL_PC Callback PC repeated. Interface: Make sure that OSCOP P runs in automatic
mode and was parameterized to be able to
receive callbacks from this device.
Check the communication link and the
callback communication parameters if
necessary.
1536 2 BATTERY Start of battery monitoring process Cyclical battery test (will be started even
without battery)
1537 2 BATTERY Start of battery monitoring after startup.
Test time:
-
1538 2 BATTERY Battery monitoring after startup OK -
1539 0 BATTERY Fault in battery monitoring after startup.
Remaining time:
-
1542 0 BATTERY Fault in battery monitoring during operation.
Remaining time:
-
1543 2 BATTERY Continuous charging started.
Charging time:
-
1545 0 BATTERY Unable to charge battery or time-out -
1547 1 BATTERY Battery fully discharged -
1548 0 BATTERY Power supply failure,
battery operation active
-
1549 1 SYSTEM Reset initiated -
1793 2 PANEL Panel button pressed -
1807 1 PANEL External reset triggered Reset trigger via control input 3
1808 1 PANEL Recording interrupted, as data can no
longer be disposed of
-
1810 1 SYSTEM Device ready Note: Some functions are ready for
operation with a delay (manual trigger,
network trigger)
1811 1 SYSTEM Power supply OK -
1812 2 SYSTEM OSCOP P communication -
1813 2 SYSTEM TAR/Analog fault recorder:
Recording event
-
1814 2 SYSTEM TPR/Frequency power recorder:
Recording event
-
1815 0 SYSTEM DAU fault DAU boot fault or DAU failure (self-
monitoring), hotline
1816 0 SYSTEM Printer fault Check printer, printer connection; fault
disappears after correction (takes approx. 5
minutes)
1818 1 SYSTEM PC unreachable Make sure that OSCOP P runs in automatic
mode and was parameterized to be able to
receive callbacks from this device.
Check the communication link and the
callback communication parameters if
necessary.
1820 1 SYSTEM Ring buffer active 90 % of the reserved TAR or TPR memory
size is reached, the oldest data will be
deleted up to 80 %.
1821 0 SYSTEM Temperature has risen above permissible
value of +55 °C
-
1822 0 SYSTEM Temperature has dropped below
permissible value of -5 °C
-
Log No. Type Class Description Comment