3 System Messages
282 Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
640 0 PARSER System parameter file fault Hotline, install SIMEAS R-PMU firmware or
OSCOP P update
641 0 PARSER Fault: System parameter file not available Hotline
642 0 PARSER Unsupported V30.xx parameters After a firmware upgrade there are still
V30.xx parameters on the device, you have
to parameterize the device (overwriting the
old parameters).
643 0 PARSER Fault: Unknown system parameter file
version
Hotline
644 0 PARSER Slot parameter file fault Hotline, install SIMEAS R-PMU firmware or
OSCOP P update
645 0 PARSER Fault: Slot parameter file not available Hotline
646 2 PARSER Slot parameter check OK -
647 2 PARSER System parameter check OK -
769 0 PRINTER Printer not connected -
770 0 PRINTER Printer switched off -
771 2 PRINTER Printer not ready -
772 0 PRINTER No printer paper -
774 0 PRINTER Printer queue: Can not open fault record.
File number:
Unable to print a fault record:
The file is damaged or deleted in ring buffer
mode.
1056 0 DAU Incomplete TAR recording. File number: TAR record cannot be used due to
inconsistent DAU data.
1057 0 DAU Incomplete TPR recording. File number: TPR record cannot be used due to
inconsistent DAU data.
1059 0 DATABAS
E
Fault writing into the database.
Recorder type:
Hotline
1060 0 DATABAS
E
Database access fault.
Recorder type:
Hotline
1061 0 DAU Wrong data block ID.
Recorder type:
TAR/TPR record cannot be used due to
inconsistent DAU data.
1062 0 DATABAS
E
Fault in message queue.
Recorder type:
Hotline
1063 0 DATABAS
E
Could not copy recording. Recorder type: Hotline
1064 0 DATABAS
E
Could not create database. Recorder type: Hotline
1065 1 DATABAS
E
Deleting recordings. Recorder type: -
1066 1 DATABAS
E
Log recorder created Log recorder created due to a firmware
upgrade.
1067 0 DATABAS
E
Database overflow, recorder type: Hotline
1068 1 DATABAS
E
Database initialized, recorder type: A new database created due to new
parameterization or a firmware upgrade.
1069 1 DATABAS
E
Deleting recordings.
Recorder type:
-
1070 1 DATABAS
E
Database initialized. Recorder type: A new database created due to new
parameterization or a firmware upgrade.
1071 0 DATABAS
E
TAR recording deleted. File number: TAR record cannot be used due to
inconsistent DAU data.
1072 0 DATABAS
E
TPR recording deleted. File number: TPR record cannot be used due to
inconsistent DAU data.
1281 2 CALL_PC Callback PC started. Interface: -
Log No. Type Class Description Comment