7
05.01
7.3 Line supply fuses, transformers and main switch
7-209
© Siemens AG 2008 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) -- 05/2008 Edition
Table 7-4 Assignment of fusible links to the NE modules
UI module
5/10 kW
UI
module
10/25 kW
UI module
28/50 kW
I/R
module
16/21 kW
I/R module
36/47 kW
I/R
module
55/71 kW
I/R
module
80/104 kW
I/R module
120/156 KW
Rated
voltage
400 V~
¡
1)
16 A D01
Neoz./
Order No.
5SE2316
25 A D02
Neoz./
Order No.
5SE2325
-- 35 A D02
Neoz./
Order No.
5SE2325
-- -- -- --
Rated
voltage
500 V~
¡
1)
16 A DII
Diazed/
Order No.
5SB261
25 A DII
Diazed/
Order No.
5SB261
80 A DIV
Diazed/
Order No.
5SC21 1
35 A DIII
Diazed/
Order No.
5SB411
80 A DIV
Diazed/
Order No.
5SC21 1
-- -- --
Rated
voltage
500 V~
¡
1)
16 A Size
00 LV
HRC/
Order No.
3NA3805
25 A Size
00 LV
HRC/
Order No.
3NA3810
80 A Size
00 LV
HRC/
Order No.
3NA3824
35 A Size
00 LV
HRC/
Order No.
3NA3814
80 A Size
00 LV
HRC/
Order No.
3NA3824
125 A
Size 00
LV HRC/
Order No.
3NA3832
160 A Size
1 LV HRC/
Order No.
3NA3136
250 A Size 1
LV HRC/
Order No.
3NA3144
Fuses for North America
Designa-
tion ¡
1)
AJT 17.5 AJT 25 AJT 80 AJT 35 AJT 80 AJT 125 AJT 175 AJT 250
Requirements for third--party fuses
I
rated
fuse 16 A 25 A 80 A 35 A 80 A 125 A 160 A 250 A
I
fuse
0.2 s 70 A 100 A 360 A 180 A 360 A 450 A 650 A 865 A
I
fuse
4s 50 A 80 A 260 A 130 A 260 A 350 A 505 A 675 A
I
fuse
10 s 42 A 65 A 200 A 100 A 200 A 250 A 360 A 480 A
I
fuse
240 s 30 A 40 A 135 A 60 A 135 A 200 A 280 A 380 A
1) Selection aid for line supply protection measures, see Table 7-3
7L
ne Su
p
p
l
y