7.3 Line supply fuses, transformers and main switch
7-210
© Siemens AG 2008 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 05/2008 Edition
Table 7-5 Assignment of circuit–breakers to the NE modules
UI module
5/10 kW
UI
module
10/25 kW
UI module
28/50 kW
I/R
module
16/21 kW
I/R module
36/47 kW
I/R
module
55/71 kW
I/R
module
80/104 kW
I/R module
120/156 KW
Circuit–
breaker
with para-
meterized
short–cir-
cuit cur-
rent
1)
3RV1031–
4BA10
3VL1702–
2DD33–
0AA0
3RV1031
–4EA10
3VL1703–
2DD33–
0AA0
3RV1041–
4LA10
3VL2708–
3DC33–
0AA0
3VL101704
–2DD33–
0AA0
3RV1031
–4FA10
3VL1703–
2DD33–
0AA0
3RV1041–
4LA10
3VL2708–
3DC33–
0AA0
3VL101704
–2DD33–
0AA0
3VL2712–
3DC33–
0AA0
3VL2716–
3DC33–
0AA0
3VL3725–
3DC36–
0AA0
Circuit–
breaker
UL ap-
proval
3)
1)
3VL2105–
2KN30–
3VL2105–
2KN30–
3VL2191–
2KN30–
3VL2105–
2KN30–
3VL2191–
2KN30–
3VL3112–
2KN30–
3VL3117–
2KN30–
3VL3125–
2KN30–
Circuit–
breaker
with RCD
combina-
tion
1)
3VL2705–
1DC33–
0AA0–Z
Z = A02
3VL2705–
1DC33–
0AA0–Z
Z = A02
3VL2708–
1DC33–
0AA0–Z
Z = A02
3VL2705–
1DC33–
0AA0–Z
Z = A02
3VL2708–
1DC33–
0AA0–Z
Z = A02
3VL2712–
1DC33–
0AA0–Z
Z = A02
3VL2716–
1DC33–
0AA0–Z
Z = A02
3VL3725–
1DC36–
0AA0–Z
Z = A02
Residual
current
monitor in-
cluding
UL
2)
1)
Residual current switch 5SM3–... + fuse RCMA470LY–21 AC/DC 30 mA – 3 A
Instrument transformer: W1–A35S internal diameter
35 mm or
instrument transformer: W2–A70SS internal diameter
70 mm
1) Selection aid for line supply protection measures, see Table 7-3
2) In combination with the appropriate circuit–breakers
3) The switches are designed for high switching capacity 65 kA at 480 V.
The connection terminals for the switches are also required.
The following box terminals, for example, are required:
for 3VL2...: two 3VL9220–4TC31 sets (one set contains three items)
for 3VL3...: two 3VL9335–4TC31 sets (one set contains three items)
!
Warning
An overdimensioning of fuses is not allowed!
When connected to line supplies with an inadequate system fault level, e.g. in
trial operation, the fuses should be dimensioned/selected so that they trip within
approx. 10 ms. If this is not the case, major device damage or fire can occur.