7.4 Line filters for I/R and UI modules
7-229
© Siemens AG 2008 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) -- 05/2008 Edition
Table 7-14 Assigning the basic line filters to the I/R modules
I/RF module
16/21 kW
I/RF module
36/47 kW
I/RF module
55/71 kW
I/RF module
80/104 kW
3)
I/RF module
120/156 kW
3)
Filter
components
Line filter
16 kW
Line filter
36 kW
Line filter
55 kW
Line filter
80 kW
Line filter
120 kW
Rated AC current 36 A 65 A 105 A
Supply voltage 3--ph. 380 V AC -- 10% ... 3 --ph. 480 V + 10%/--15% < 1 min) (TN line supply)
1)
; 47 ... 63
Hz
Order number 6SL3000--
0BE21--6DAV
6SL3000--
0BE23--6DAV
6SL3000--
0BE25--5DAV
Mounting position W all or base/floor mounting, refer to Fig. 7-13
Dimensions (W x H x D),
approx.
50x429x226 75x433x226 100x466x226
Module width Refer to dimension drawings, Chapter 12
Weight, filter 5kg 6.5 kg 11.5 kg
Power loss 16 W 28 W 41 W
Connection 10 mm
2
/1.5 Nm
PE, M6 studs
/3 Nm
2)
35 mm
2
PE, M6 studs
/3 Nm
2)
50 mm
2
PE, M6 studs
/3 Nm
2)
Terminals
Line supply connection
(line)
L1, L2, L3, PE L1, L2, L3, PE L1, L2, L3, PE
Terminals
Load connection (load)
L1’, L2’, L3’, PE L1’, L2’, L3’, PE L1’, L2’, L3’, PE
I
rated
fuse
4)
35 A 80 A 125 A
Compatibility, residual cur-
rent protective devices
The discharge current is limited to approx. 110 mA in
conjunction with a universally current sensitive resid-
ual current protective device and Siemens cables and
the 150 m cable.
Permissible
ambient temperature
S Operation [°C]
S Storage/transport [°C]
0 ... +40; maximum +55 at 0.6 P
rated
of the l/R module
--25 ... +70
Cooler Natural ventilation
Degree of protection to EN
60529 (IEC 60529)
IP20
EN 5501 1 radio interfer-
ence suppression
Limit value Class A for cable--borne interference if systems are engineered according to
the Configuration Manual
Limit value Class B for cable--borne faults and disturbances on request
1) The permissible supply voltage of the system depends on the infeed module used.
2) For ring terminal end in accordance with DIN 46234
3) Being prepared
4) The fuse used must have this rated current. Recommendations for the fuses, refer to Table 7-4.
7L
ne Su
p
p
l
y
Connec
t
on11.0502.07