EasyManua.ls Logo

Siemens SIMODRIVE 611 universal - Page 152

Siemens SIMODRIVE 611 universal
930 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4
01.99
4.7 Induction motor operation with induction motor
4-152
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
Table 4-7 Parameter overview for IM operation (encoderless operation)
Parameters
No. Name Min. Standard Max. Units Effec-
tive
1451:8 P gain, speed controller IM (ARM) 0.0 0.3 9 999.999 Nms/rad Imme-
diately
... the P gain of the speed controller in IM operation is set (operation without encoder).
Note:
The parameter is preset when executing the ”calculate controller data”/”calculate unlisted
motor” function.
1453:8 Integral action time, speed controller IM
(ARM)
0.0 140.0 6 000.0 ms Imme-
diately
... the integral action time of the speed controller is set in IM operation (operation without en-
coder).
Note:
The parameter is preset when executing the ”calculate controller data”/”calculate unlisted
motor” function.
1458 Current setpoint open–loop controlled
range IM (ARM)
0.0 90.0 150.0 % Imme-
diately
For pure IM operation (P1465 = 0), the drive is open–loop, current–frequency controlled below
the changeover speed (P1466).
In order to be able to accept a higher load torque, the motor current in this range can be in-
creased using P1458.
Note:
This is entered as a percentage of the rated motor current (P1103).
The current is limited to 90% of the current limit value (P1238).
1459 Torque smoothing time constant AM (ARM) 0.0 4.0 100.0 ms Imme-
diately
... the pre–control value for the torque is smoothed (initial rounding–off).
Note:
In IM operation, a speed–torque–frequency pre–control is implemented due to the low dynamic
performance.
1465 Changeover speed MSD/IM (ARM) 0.0 100 000.0 100 000.0 RPM Imme-
diately
Above this, the drive runs, in IM operation with the speed set in this parameter.
P1465 = 0 pure IM operation
P1466 < P1465 < n
max
mixed operation, MSD/IM
P1465 > n
max
only MSD operation
Note:
When IM operation is selected, only pulse frequencies (P1100) of 4 and 8 kHz are permissi-
ble.
The parameter is preset to 0 when first commissioning, if there is no motor measuring
system (P1006 = 98, P1027.5 = 1).
1466 Changeover speed, closed–loop/open–
loop control IM (ARM)
150.0 300.0 100 000.0 RPM Imme-
diately
For pure IM operation (P1465 = 0), the drive is open–loop, current–frequency controlled below
the speed set using this parameter.
Note:
The parameter is preset when executing the ”calculate controller data”/”calculate unlisted
motor” function.
4 Commissioning

Table of Contents

Related product manuals