4.10 Linear motors (1FN1, 1FN3 motors)
4-178
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
8. Set the setpoint limit switch
P0314, P0315 and P0316
(refer under the index entry ”Software limit switch”)
9. Optimizing the axis controller settings
Note:
Generally, the automatic controller setting for linear motors does not
provide adequate results, as the measuring system mounting plays
a significant role in the closed–loop control characteristics.
Current and speed controllers (refer to Chapter 6.1.4)
Position controller (refer under the index entry
”Kv factor”)
10.Check and set the rotor position identification
To check the rotor position identification, using a test function,
you can determine the difference between the calculated rotor
angle position and that actually used by the closed–loop control.
Proceed as follows:
Start the test function several times and evaluate the difference
Start Set P1736 (test rotor position identification) to 1
Difference P1737 (difference, rotor position identification)
= _ _ _ _ , _ _ _ _ , _ _ _ _ , _ _ _ _ , _ _ _ _
Is the spread of the measured values less than 10 degrees elec-
trical?
Yes: OK
No: Increase P1019 (e.g. by 10 %)
and repeat the measurements
If OK after having repeated the measurements, then the
angular commutation offset can be re–determined:
For an incremental measuring system
(incremental – one zero mark):
as for Point 5. (determining the angular commutation off-
set)
For an absolute measuring system:
Power–down the drive (POWER ON–RESET)
Power–up the drive with the pulse or controller enable
signals switched–out
Set P1017.0 to 1
Switch–in the pulse and enable signals
––> The angular offset is automatically
entered into P1016
––> Fault 799
(Save to FEPROM and HW–RESET required)
is displayed
Save to FEPROM and carry–out a HW–RESET
For incremental measuring system
(incremental – no or several zero marks):
Save to FEPROM and carry–out a HW RESET
4 Commissioning