5
5.7 Settings at the PROFIBUS DP master
5-292
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
The sent and received process data of the ”DP slaves 611U” are dis-
played using the following parameters:
P1788:17 Received process data PROFIBUS
P1789:17 Sent process data PROFIBUS
The sent and received PKW data of the ”DP slave 611U” are displayed
using the following parameters:
P1786:5 Received PKW data PROFIBUS
P1787:5 Sent PKW data PROFIBUS
The parameterizing and configuration data, received from the DP
master, are displayed using the following parameters:
P1783:64 received PROFIBUS parameterizing data
P1784:64 received PROFIBUS configuration data
Diagnostics of the
process data
Diagnostics of the
PKW data
(from SW 2.4)
Diagnostics of the
parameterizing
and
configuration
data
(from SW 3.1)
5 Communications via PROFIBUS DP
04.9910.99