EasyManua.ls Logo

Siemens SIMODRIVE 611 universal - Page 335

Siemens SIMODRIVE 611 universal
930 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6
6.1 Operating mode, speed/torque setpoint (P0700 = 1)
6-335
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
For the ramp–function generator, the following signals are used:
Input signal – Ramp–function generator enable
– Ramp–up time zero
– Ramp–up time zero for contr. enable (from SW 3.1)
Output signal – Ramp–up completed
Readers note
The signals can be entered or output as follows:
via terminals ––> refer to Chapter 6.4.2 or 6.4.5
via PROFIBUS–DP ––> refer to Chapter 5.6.1
All of the input/output signals are shown and described in Chapter
6.4.3 and 6.4.6 and can be found in the Index under ”Input signal...” or
”Output signal...”.
Ramp–function
generation
active
n
set
Tolerance bandwidth P1426
Ramp–up
completed
| M | < M
x
n
set
n
act
Threshold P1428
Torque
Delay time P1427
Delay time P1429
P1427
P1427
n
set
= n
act
RFG input
RFG output
P1426
from here onwards, | M | < Mx evaluation
1) For an active average–value filter for the speed setpoint (P1012.8=1), a setpoint step somewhat
greater than P1426 must be used in order to clearly identify the start of a new ramp–up operation.
Fig. 6-5 Signal characteristics for the ramp–function generator
Input/output
signals for the
ramp–function
generator
6 Description of the Functions
01.99
07.03

Table of Contents

Related product manuals