6.2 Positioning mode (P0700 = 3, from SW 2.1)
6-400
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
The following sequence is practical when adjusting absolute value en-
coders:
1. Traverse the axis to a known or measured position (this is the re-
quired actual value).
The axis can be traversed, e.g. using ”Jogging 1” or ”Jogging 2”.
2. Set P0160 to ”required actual value”
3. Set P0175 = 1
The ”SIMODRIVE 611 universal” drive determines the difference
between the required actual value in P0160 and the encoder actual
value and enters it into an internal parameter.
If a fault occurs, then P0175 is set to –1.
If the operation was error–free, then P0175 is set to 2, 3 or 4 (refer
to Chapter 6.2.8) and Fault 799 (save to FEPROM and HW RESET
required) is signaled.
Save parameters in the FEPROM (P0652 = 1)
Carry–out a HW–RESET (press the POWER–ON RESET button
on the front panel of the control board)
4. Test: Is the actual value correctly displayed after power–on?
The absolute value encoder is adjusted, supported by the operator.
The following sequence is practical:
1. Establish online operation between SimoCom U and the drive
2. Traverse the axis to a known or measured position (this is the re-
quired actual value).
The axis can be traversed, e.g. using ”Jogging 1” or ”Jogging 2”.
3. Select the ”referencing” dialog box
Enter the ”required actual value” into the appropriate field.
Set ”Absolute value” button
The ”SIMODRIVE 611 universal” drive determines the difference
between the required actual value in P0160 and the encoder ac-
tual value and enters it into an internal parameter.
If this operation is error–free, fault 799 is then signaled (save to
FEPROM and HW–RESET) and the operator is prompted to:
Save parameters in the ”FEPROM”
and
carry out a ”HW–RESET”
4. Test: Is the actual value correctly displayed after power–on?
Procedure
to adjust an
absolute value
encoder
using the display
and operator
control unit
Procedure when
adjusting an
absolute value
encoder
using SimoCom U