EasyManua.ls Logo

Siemens SIMODRIVE 611 universal - Page 618

Siemens SIMODRIVE 611 universal
930 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6
6.16 Rotor position synchronization/rotor position identification
6-618
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
The following should be done if faults occur:
Fault 611 (inadmissible motion):
––> Increase the parameterized load mass (P1076), check the max-
imum permissible motion (P1020) and if required, increase.
Fault 610 (rotor position identification unsuccessful) and P1734 = –4
(current rise too low):
––> The motor is not correctly connected
––> The motor power connections must be checked.
Fault 610 (rotor position identification unsuccessful) and P1734 = –6
(max. permissible duration exceeded):
––> This can be due to the following reasons:
external forces have faulted the identification routine (e.g.
coupled axes have not been opened, surges, etc.),
if the drive emits an excessive noise (a loud whistling sound) dur-
ing the identification routine, then the identification technique has
become unstable:
––> P1076 must be reduced,
Extremely low encoder resolution:
––> use an encoder with a higher resolution
encoder mounting is not stiff enough:
––> improve the mounting.
Fault 610 (rotor position identification unsuccessful) and P1734 = –7
(no clear rotor position has been found:
––> This can be due to the following reasons:
the axis cannot freely move (e.g. the motor rotor is locked)
external forces have disturbed the identification routine (refer
above)
the axis has an extremely high friction:
––> the identification current (P1019) must be increased
If the rotor position identification routine was successful, the rotor posi-
tion which was found should be checked. This test function can deter-
mine the difference between the determined rotor position angle and
the rotor position angle used by the closed–loop control.
The following procedure should be applied several times:
1. Start the test function using P1736 = 1.
2. Evaluate the difference in P1737 – a spread of the measured values
of less than 10 degrees is acceptable. If this is not the case, then a
higher current must be used for the identification routine (P1019).
6 Description of the Functions
08.02

Table of Contents

Related product manuals