7.3 List of faults and warnings
7-628
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
7.3 List of faults and warnings
7.3.1 Fault without a number being displayed
Fault After power–on, the operating display is inactive
Cause At least 2 phases are missing (NE module)
At least 2 input fuses have ruptured (NE module)
Defective electronics power supply in the NE module
Equipment bus connection (ribbon cable) from
the NE module to the ”SIMODRIVE 611 universal”
control board is either not inserted or defective
Defective control board
Fault After the controller enable, the motor is stationary at
n
set
0
Cause P1401:8 is set to zero
Power–on inhibit is present for PROFIBUS operation
Remove the power–on inhibit with
A ”high – low – high” signal change at 65.x or
the control bit STW1.0 (ON/OFF 1)
or
set bit 12 of parameter 1012 to zero
Fault After the controller has been enabled, the motor briefly
moves
Cause Defective power module
Fault After the controller has
been enabled, the motor rotates at max. 50 RPM at n
set
> 50 RPM or
the motor oscillates at n
set
< 50 RPM
Cause Motor phase sequence is incorrect (interchange 2 phase connections)
The entered encoder pulse number was too high
Fault After the controller is enabled, the motor accelerates
to a high speed
Cause Encoder pulse number too small
Open–loop torque controlled mode selection?
Fault ”– – – – – –” is output on the display unit
Cause There is no drive firmware in this memory module.
Remedy, refer to fault 001