030 S7 communication error. Supplementary info: \%X
Cause A fatal communication error was identified, or the drive software is no
longer consistent. The cause is erroneous communications or a hard-
ware fault on the control module.
Supplementary information: only for siemens-internal error diagnostics
Remedy – Implement noise suppression measures (screening, check ground
connections, ...)
– Replace control module
Acknowledgement POWER ON
Stop response STOP II (SRM, SLM) STOP I (ARM)
031 Internal data error. Suppl. info: \%X
Cause Error in the internal data, e.g. errors in the element/block lists (incorrect
formats, ...). The drive software is no longer consistant. The cause is
propably a hardware fault on the control module.
Supplementary information: only for siemens-internal error diagnostics
Remedy – Re-load drive software
– Replace control module
Acknowledgement POWER ON
Stop response STOP II (SRM, SLM) STOP I (ARM)
032 Incorrect number of current setpoint filters
Cause An illegal number of current setpoint filters was entered (> 4) (maxi-
mum number = 4).
Remedy Correct number of current setpoint filters (P1200).
Acknowledgement POWER ON
Stop response STOP II (SRM, SLM) STOP I (ARM)
033 Incorrect number of speed setpoint filters
Cause An inadmissible number of speed setpoint filters (> 2) was entered
(max. number = 2).
Remedy Correct number of speed setpoint filters (P1500)
Acknowledgement POWER ON
Stop response STOP II (SRM, SLM) STOP I (ARM)
034 Axis count function has failed
Cause The function for determining the number of axes that physically exist on
the power section has calculated an illegal value.
Remedy Check that the control module is correctly inserted in the power section
or whether the power section is defective.
Acknowledgement POWER ON
Stop response STOP II (SRM, SLM) STOP I (ARM)