7.3 List of faults and warnings
7-696
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
795 Ang. encoder, pos. ref. value normalization factor too
large. Suppl. info: \%u
Cause The position reference value normalization for the angular encoder in-
terface is not permissible.
Supplementary info
= 1 ––> Condition P0401 * P0895 < 8388608 violated
= 2 ––> Condition P0402 * P0896 < 8388608 violated
Remedy Check parameterization via P0401, P0402, P0895 and P0896. It may
be possible to achieve the conditions above by shortening the numera-
tor P0401 * P0895 with the denominator P0402 * P0896.
Acknowledgement POWER ON
Stop response STOP II
797 Error in center frequency measurement
Cause The speed was too high during the center frequency measurement
(current calibration). The center frequency is measured automatically at
run-up, or when the pulses are inhibited.
Remedy Power up the drive converter if the motor runs at a reduced speed.
Acknowledgement POWER ON
Stop response STOP I
798 Measured value memory active
Cause The measured-value memory was active during power-up.
Remedy Run up again.
Acknowledgement POWER ON
Stop response STOP I
799 FEPROM backup and HW Reset required
Cause Parameters were re-calculated. Parameters must be saved and the
module run up again after this new calculation.
Remedy The newly calculated data should be saved in the FEPROM. The new
parameters become effective the next time that the module runs up!
Acknowledgement POWER ON
Stop response STOP II (SRM, SLM) STOP I (ARM)
800 Minus hardware limit switch
Cause A 1/0 edge was identified at the ”Minus hardware limit switch” input signal.
Remedy – In the pos mode: Return the drive to the traversing range using jog
key 1 or 2.
– In the n-set mode: Enter a setpoint that opposes the approach direction.
Acknowledgement not required
Stop response STOP VII