7.3 List of faults and warnings
7-702
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
829 PROFIBUS: Illegal parameterization received. Reason:
\%u
Cause An illegal parameterizing frame was received via PROFIBUS. Cyclic
data transfer cannot start.
Reasons:
8 = The parameterizing telegram has an illegal length
9 = The length data in the equidistant block is illegal
10 = A block header has an unknown ID.
11 = The basis time Tbasedp is not permissible (not equal to 125 us).
12 = The DP clock cycle Tdp is not permissible (less than 1ms or
greater than 32ms).
13 = The time Tmapc is less than 1*Tdp or greater than 14*Tdp.
14 = The base time Tbaseio is not permissible (not equal to 125us).
15 = Time Ti is greater than the DP clock cycle (Tdp).
16 = Time To is greater than the DP clock cycle (Tdp).
17 = For active Data Exchange, a new parameterization was received
with different contents.
18 = Clock cycle synchronous operation was selected without a
suitable option module having been activated (refer to P0875).
19 = IsoM_Req (state 3, bit 4) is requested in the DPV1 header without
there being an isochron block (ID 0x04).
20 = Fail_Safe (state 1, bit 6), IsoM_Req (state 3, bit 4) or
Prm_Structure (state 3, bit3) missing in the DPV1 header although
an isochron block (ID 0x04) is available.
21 = The time Tdx is greater than (To – 125us) or greater than
(Tdp – 250us).
22 = The time Tpllw is greater than 1us.
23 = Slave-to-slave communication access target address and length
do not conform to word boundary.
24 = Maximum number (3 external + 1 internal) of slave-to-slave
communication links has been exceeded.
25 = Maximum number (8) of accesses per link has been exceeded.
26 = Unknown version ID in the slave-to-slave communications block.
27 = The maximum overall length of the filter table has been exceeded.
31 = The permitted maximum length of the parameterizing telegram for
the option module has been exceeded.
32 = The option module firmware does not support slave-to-slave
communications
Remedy Check the bus configuration at the master, and if required correct the
parameterization.
If required, insert (reason 18) a suitable option module and activate.
If required, (reason 31 or reason 32) upgrade the option module firm-
ware to a version greater than or equal to 04.01.
Acknowledgement not required
Stop response STOP VII
7 Fault Handling/Diagnostics
01.99
04.05