7.3 List of faults and warnings
7-705
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
833 PROFIBUS: No connection to the publisher \%u
Cause Cyclic data transfer between this slave and a slave-to-slave commu-
nications publisher was still not started or was interrupted.
Examples:
– Bus connection interrupted
– Publisher failure
– Master runs up again
– The response monitoring (Watchdog) for this slave was de-activated
via the parameterizing telegram (SetPrm) (Diagnostics: P1783:1
bit 3 = 0).
Supplementary info: PROFIBUS address of the publisher
Remedy Check the publisher and bus connections to the publisher, to the
master and between the master and publisher.
if the watchdog is de-activated, activate the response monitoring for
this slave via Drive ES.
Acknowledgement not required
Stop response STOP VII
840 Teach-in for running traversing program
Cause Teach-in was requested during a running traversing program.
Remedy Exit the traversing program and re-request teach-in.
Acknowledgement not required
Stop response STOP VII
841 Teach-in for relative block
Cause The traversing block as ”teach in block” is relative instead of absolute.
Remedy Change the traversing block mode ”teach in block” from relative to ab-
solute.
Acknowledgement not required
Stop response STOP VII
842 Teach-in for a relative standard block
Cause The traversing block as ”teach in standard set”, is relative instead of
absolute.
Remedy Change the traversing block mode ”teach in standard block” from rela-
tive to absolute.
Acknowledgement not required
Stop response STOP VII
7 Fault Handling/Diagnostics
01.99
04.05