7.3 List of faults and warnings
7-707
 Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
865 Invalid signal number
Cause The signal number for the analog output is not permissible.
An analog value can be output for diagnostic, service and optimization
tasks
Term. 75.x/15, 16.x/15, DAC1, DAC2
Remedy Enter valid signal number
(refer to the Description of Functions SIMODRIVE 611 universal)
Acknowledgement not required
Stop response STOP VII
866 Parameterizing error, current controller adaption
Cause For the current controller adaption, the upper current limit (P1181) was
parameterized with a lower value than the lower current limit (P1180).
Adaption is de-activated when the parameterizing error is output.
Remedy P1181 must contain a higher value than P1180.
Acknowledgement not required
Stop response STOP VII
867 Generator mode: Response voltage > shutdown
threshold
Cause The sum of the values in P1631 + P1632 is greater than the value in
P1633.
Remedy Appropriately change P1631, P1632 and P1633.
Note:
P1631 to P1633 being prepared
Acknowledgement not required
Stop response STOP VII
868 Generator mode: Response voltage > monitoring
threshold
Cause The input value for the threshold voltage (P1631) is greater than the
value in P1630.
Remedy Change the drive parameters.
Note:
P1630 and P1631 being prepared
Acknowledgement not required
Stop response STOP VII