A.1 Parameter list
A-751
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
0238:8 Load revolutions
Min Standard Max Unit Data type Effective
1 1 8388607 Unsigned32 PO
... specifies the ratio (Ü) between the encoder and load.
Ü = P0237:8 / P0238:8
Note: refer to the index entry ”Encoder adaptation”
0239 Re-reference or re-adjust only if necessary (–> 4.1)
Min Standard Max Unit Data type Effective
0 0 1 Unsigned16 immed.
0 Referencing or adjustment is withdrawn when changing the parameter set (standard)
1 Referencing or adjustment is only withdrawn when the parameter set is changed if the
mechanical ratio (Ü = P0237:8 / P0238:8) changes.
Note: refer under the index entry ”Referencing or adjustment”
0241 Activating, modulo conversion, rotary axis (SRM ARM) (–> 2.4)
Min Standard Max Unit Data type Effective
0 0 1 Unsigned16 PO (SRM ARM)
1 Modulo conversion activated, modulo correction is executed according to P0242
0 Modulo conversion de-activated
Note:
refer to the index entry ”rotary axis with modulo offset”
0242 Modulo range, rotary axis (SRM ARM) (–> 2.4)
Min Standard Max Unit Data type Effective
1 360000 100000000 MSR Unsigned32 PO (SRM ARM)
... defines the modulo range of the rotary axis.
Practical modulo range values are: n * 360 degrees with n = 1, 2, ...
Note:
refer to the index entry ”rotary axis with modulo offset”
0250 Activate direct measuring system (SRM ARM) (–> 3.3)
Min Standard Max Unit Data type Effective
0 0 1 Unsigned16 PO (SRM ARM)
... the direct measuring system at X412 is activated/deactivated for drive A.
1 Direct measuring system activated (only drive A)
0 Direct measuring system deactivated
Note:
refer to the index entry ”Direct measuring system”
0310 Cam switching position 1
Min Standard Max Unit Data type Effective
–200000000 0 200000000 MSR Integer32 immed.
... the cam switching position 1 is set.
Note: refer to the index entry ”Position-related switching signals (cams)”
0311 Cam switching position 2
Min Standard Max Unit Data type Effective
–200000000 0 200000000 MSR Integer32 immed.
... the cam switching position 2 is set.
Note: refer to the index entry ”Position-related switching signals (cams)”
A Lists
01.99
! 611ue diff !
04.05