2.3 Connection diagram and wiring
2-76
Siemens AG 2005 All Rights Reserved
SIMODRIVE 611 universal Description of Functions (FBU) – 04.05 Edition
Table 2-4 Overview of the drive–specific terminals, continued
Terminals Technical dataType
1)
Function
Drive A
Technical dataType
1)
Function
Drive B
No.
Technical dataType
1)
Function
Desig-
nation
No.Desig-
nation
Terminals for analog inputs and digital inputs/outputs (X451, X452)
X451 X452
Connector type: 10–pin conn. strip
Max. conductor cross–section for finely–stranded or solid conduc-
tors: 0.5 mm
2
56.A X451.1 56.B X452.1 Analog input 1 AI Differential input
Voltage range
14.A X451.2 14.B X452.2 Reference 1
Voltage range
(limit values): –12.5 V to +12.5 V
Input resistance: 100 k
24.A X451.3 24.B X452.3 Analog input 2
Input resistance: 100 k
Resolution: 14 bits (sign + 13 bits)
Wiring: Connect the cable with the
20.A X451.4 20.B X452.4 Reference 2
Wiring: Connect the cable with the
braided shield at both ends
65.A X451.5 65.B X452.5 Controller enable
drive–specific
I Typ. curr. consumption: 6 mA at 24 V
Signal level (incl. ripple)
High signal level: 15 V to 30 V
Low signal level: –3 V to 5 V
Electrical isolation:
Ref. is T. 19/T. M24
9 X451.6 9 X452.6 Enable voltage
(+24 V)
S Reference: Terminal 19
Maximum current
(for the total group): 500 mA
Note:
The enable voltage (terminal 9) can
be used to supply the enable signals
(e.g. controller enable).
I0.A X451.7 I0.B X452.7 Digital input 0
2)
Fast input
3)
e.g. for
equivalent zero
mark, external
block change (from
SW 3.1)
DI Voltage: 24 V
Typ. current consumption:
8.6 mA at 24 V
Signal level (incl. ripple)
High signal level: 15 V to 30 V
Low signal level: –3 V to 5 V
Electrical isolation:
Ref. is T. 19/T. M24
I1.A X451.8 I1.B X452.8 Digital input 1
2)
DI
Ref. is T. 19/T. M24
Note:
Parameterization of the input ter-
minals and the standard assign-
I2.A X451.9 I2.B X452.9 Digital input 2
2)
DI
minals and the standard assign-
ment is described in
Chapter 6.4.2.
I3.A X451.10 I3.B X452.10 Digital input 3
2)
DI
Chapter 6.4.2.
An open–circuit input is
interpreted as 0 signal.
1) I: Input; DI: Digital input; AI: Analog input; S: Supply,
2) Can be freely parameterized
All of the digital inputs are de–bounced per software. For the signal detection, this results in a delay time
of between 1 and 2 interpolation clock cycles (P1010).