4. Press the ▼ function key to select the <Control settings> entry from this menu. The display
changes to the Control settings menu.
Ⴍ
&RQWUROVHWWLQJV
6DYH/2&$/PRGH
2IILQ5(027(
/2&$/5(027(DOVRGXULQJRSHU
5HG2))NH\DFWVDV
+HOS
%DFN
ႱႧ&KDQJH
DNWLY
ႱႧ
1R
ႱႧ
1R
ႱႧ
1R
ႱႧ
2))
5. Press the or function key to select the desired entry. Press the <Change> function key
to change the setting.
6. Press the <Back> function key to confirm the entries.
You can find the description and setting options for the individual menu items in the following.
Saving LOCAL mode
Setting "Yes" (default setting):
The LOCAL operating status is saved when the power supply is switched off and restored
the next time power is switched on.
Setting "No":
The REMOTE operating status is activated when the supply voltage is switched back on.
Off in remote
Setting "Yes":
It is possible to switch off in remote mode by pressing the <OFF> key.
Setting "No":
The <OFF> key has no effect in remote operation.
The <OFF> key is always active in LOCAL mode.
LOCAL/REMOTE also during operation
Setting "Yes":
You can switch between LOCAL and REMOTE when the drive is switched on (i.e. motor
is running).
Setting "No" (default setting):
Before the system switches to LOCAL, a check is carried out to determine whether the drive
is in the operational status. In this case, the system does not switch to LOCAL and outputs
the error message "Local mode during operation not possible". Before the system switches
to REMOTE, the drive is switched off and the setpoint is set to 0.
Operation
8.2 Operation via the AOP30 operator panel
SINAMICS GM150 6SL3815-2LN41-4AA2
136 Operating Instructions 04/2017