Red OFF key acts as
OFF1 - Ramp-down on the deceleration ramp (p1121). OFF1 is the default setting.
OFF2 - Immediate pulse block, motor coasts to a standstill.
OFF3 - Ramp-down on the emergency stop ramp (p1135).
The OFF key is only effective in LOCAL mode.
Red OFF key also in REMOTE
Setting "Yes":
It is possible to switch off in remote mode by pressing the <OFF> key.
Setting "No":
The <OFF> key has no effect in REMOTE operation.
In LOCAL mode, the OFF key is always in effect.
Clockwise/counter-clockwise switchover
Setting "Yes":
In LOCAL mode, left/right switching is possible using the
key.
Setting "No" (default setting):
The key does not act in LOCAL mode.
In REMOTE mode, the key is always in effect.
For safety reasons, the left/right key is inactive in the default setting. Pumps and fans may
normally be operated only in one rotational direction. In the "Operation" state in LOCAL mode,
the current rotational direction is indicated by an arrow next to the operating mode.
JOG key active (jogging)
Setting "Yes":
In LOCAL mode, in the "Ready to switch on" state (not in "Operation" state), jogging mode
is possible using the <JOG> key. The speed set in parameter p1058 is approached.
Setting "No":
The <JOG> key has no effect in LOCAL mode.
The <JOG> key never acts in REMOTE mode.
Operation
8.2 Operation via the AOP30 operator panel
SINAMICS GM150 6SL3815-2LN41-4AA2
Operating Instructions 04/2017 137