Recommended interconnection rules 
The following recommended rules should be observed for the DRIVE-CLiQ wiring: 
●  The following applies to all DRIVE-CLiQ components with the exception of the Control 
Unit: The DRIVE-CLiQ sockets Xx00 are DRIVE-CLiQ inputs (Uplink), the other DRIVE-
CLiQ sockets are outputs (Downlink). 
–  The DRIVE-CLiQ cable from the Control Unit should be connected to DRIVE-CLiQ 
socket X200 on the first booksize power unit or X400 on the first chassis power unit. 
–  The DRIVE-CLiQ connections between the power units should each be connected 
from the DRIVE-CLiQ sockets X201 to X200 and/or X401 to X400 on the follow-on 
component. 
●  A single Line Module should be connected directly to the Control Unit (recommended 
DRIVE-CLiQ socket: X100). 
–  Several Line Modules should be connected in series. 
●  No more than 6 Motor Modules should be connected to a DRIVE-CLiQ line on the Control 
Unit (including with vector, V/f control). 
●  Motor Modules should be connected directly to the Control Unit in vector control. 
–  If DRIVE-CLiQ socket X100 is already assigned to a Line Module, DRIVE-CLiQ socket 
X101 should be used. 
–  Several Motor Modules should be connected in a line. 
●  In servo control, Motor Modules should be connected to a DRIVE-CLiQ line together with 
the Line Module. 
–  Several Motor Modules should be connected in a line. 
–  If there is already a Line Module present, the first Motor Module should be connected 
in line to socket X201 of the Line Module. 
–  If there is no Line Module present, the first Motor Module should be connected directly 
to the Control Unit (recommended DRIVE-CLiQ socket: X100). 
●  If the Motor Modules need to be distributed across two DRIVE-CLiQ lines (e.g. on 
account of the predetermined current controller sampling times), the next higher DRIVE-
CLiQ socket on the Control Unit should be used. 
Example, vector control in the chassis format: 
–  Active Line Module current controller sampling time 400 µs: X100 
–  Motor Modules current controller sampling time 250 µs: X101 
–  Motor Modules current controller sampling time 400 µs: X102 
●  Only one end node should be connected to free DRIVE-CLiQ sockets within a DRIVE-
CLiQ line (e.g. Motor Modules wired in a line), for example, one Sensor Module or one 
Terminal Module, without routing to additional components.