Function modules
8.11 Extended stop and retract
Drive functions
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
577
Triggering for all drives of a Control Unit
Conditions for triggering the function:
ESR function has been configured in the drive, e.g. stopping or retraction.
ESR function has been enabled in the drive.
The pulse enable has been set.
A distinction is made between the following fault sources:
Communication failure:
The Control Unit detects the communication failure and triggers autonomous reactions
in all the enabled drives.
A status checkback signal is no longer possible.
The higher-level control removes the "Master control by PLC" signal (F07220).
Interruption of data transmission via the fieldbus (F01910 or F08501).
External trigger signal
An external trigger signal from the control triggers the ESR function via the telegrams
390, 391 or 392.
8.11.3
Invalid sources
The following DRIVE-CLiQ communication failures do not produce an ESR trigger:
Pulse suppression of the motor modules is present
The drive switches to OFF2 and coasts to a standstill.
Failure of encoder modules as motor measuring system
The system is switched to operation without encoder and a parameterized stop response
is initiated.
Failure of encoder modules as a direct application-specific measuring system
The application is shut down and a parameterized stop response is initiated.