Monitoring functions and protective functions
9.4 Stall protection (vector control only)
Drive functions
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
639
9.4
Stall protection (vector control only)
If the adaptation controller output exceeds the speed threshold set in p1744 for stall
detection, then r1408.11 (speed adaptation, speed deviation) is set.
If the error threshold value set in p1745 is exceeded when in the low speed range (less than
p1755 · (100% - p1756)), then r1408.12 (motor stalled) is set.
If one of the two signals is set, then after the delay time in p2178, fault F7902 (motor stalled)
is output.
Figure 9-2 Stall protection
Function diagrams (see SINAMICS S120/S150 List Manual)
6730
Vector control
- Interface to Motor Module (ASM, p0300 = 1)
8012
Signals and monitoring functions
- Torque messages, motor locked/stalled
Overview of important parameters (see SINAMICS S120/S150 List Manual)
r1408.0...15
CO/BO: Status word, current controller
p1744[0...n]
Motor model speed threshold stall detection
p1745[0...n]
Motor model error threshol
d stall detection
p1755[0...n]
Motor model changeover speed encoderless operation
p1756
Motor model changeover speed encoderless operation
p2178[0...n]
Motor stalled delay time