Function modules
8.10 Parallel connection of power units
Drive functions
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
559
8.10
Parallel connection of power units
In order to extend the power range, SINAMICS S120 supports the parallel connection of
identical power units such as Line Modules and/or Motor Modules. The prerequisites for
connecting power units in parallel are as follows:
Same type
Same type rating
Same rated voltage
Same firmware version
Chassis or cabinet format
The Motor Modules must be operated in vector control
It makes sense to connect Line Modules and Motor Modules in parallel for the following
reasons:
To boost the converter output if it is not technically or economically feasible to achieve the
required power by any other means.
To increase the availability, for example, to maintain emergency operation (possibly also
at a lower rating), if a power unit fails.
Parallel operation is not released under the following conditions:
Combining different types of Infeed Module within the same parallel connection (e.g.
Basic Line Modules with Smart Line Modules or Basic Line Modules with Active Line
Modules).
Motor Modules in servo control
Infeed Modules and Motor Modules in the booksize and blocksize formats