Communication
11.5 Communication via EtherNet/IP
Drive functions
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
873
11.5
Communication via EtherNet/IP
11.5.1
Overview
EtherNet/IP (short: EIP) is real-time Ethernet, and is mainly used in automation technology.
Communication via EtherNet/IP is possible via the following connection(s):
Via the Option Board Ethernet CBE20
Possible drive units:
CU320-2 PN
CU320-2 DP
11.5.2
Connect drive device to Ethernet/IP
In order that your drive can be connected to a control system via Ethernet, your control
system requires a generic I/O module for cyclic communication via EtherNet/IP. You
manually create this generic I/O module in the control system.
Create generic I/O module and connect the drive to the control system
To connect the drive to a control system via Ethernet, proceed as follows:
1. Connect the drive to the control system via an Ethernet cable.
2. In your control, create a generic I/O module with EtherNet/IP functionality.
Insert a new module in your control system.
Select a generic Ethernet module from the selection.
Enter the network parameters for the newly inserted module (IP address, subnet
mask, standard gateway, station name).