EasyManua.ls Logo

Siemens SINAMICS S120 - Measurement with up to 6 Channels; Measurement with up to 12 Channels

Siemens SINAMICS S120
1094 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Monitoring functions and protective functions
9.5 Thermal motor protection
Drive functions
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
657
9.5.7.1
Measurement with up to 6 channels
Temperature measurement with a 2-wire sensor
With p4108[0...5] = 0, you evaluate a sensor in a 2-wire system at a 4-wire connection at
terminals 1 and 2. Terminals 3 and 4 remain open.
Temperature measurement with a 3-wire sensor
With p4108[0...5] = 2, you evaluate a sensor in a 3-wire system at a 4-wire connection at
terminals 3 and 4. The measuring cable is connected at terminal 1. You must short-circuit
terminals 2 and 4.
Temperature measurement with a 4-wire sensor
With p4108[0...5] = 3, you evaluate a sensor in a 4-wire system at a 4-wire connection at
terminals 3 and 4. The measuring cable is connected at terminals 1 and 2.
You can find additional information in function diagram 9626 in the SINAMICS S120/S150
List Manual.
9.5.7.2
Measurement with up to 12 channels
Temperature measurement with two 2-wire sensors
With p4108[0...5] = 1 you can acquire the signals from two sensors in 2-wire technology. The
first sensor is connected to terminals 1 and 2. The 2nd sensor (number = first sensor + 6) is
connected at terminals 3 and 4. You can find additional information in function diagram 9627
in the SINAMICS S120/S150 List Manual.
When connecting 2 2 wire sensors to terminal X531, the 1st sensor is assigned to
temperature channel 1. The 2nd sensor is assigned to channel 7 (1+6).
Up to 12 temperature sensors can be connected to a TM150.
Note
Connection diagram for 12 temperature channels
The temperature sensors connected to a TM150 are not numbered consecutively. The first 6
temperature channels retain their numbering of 0 to 5. The other 6 temperature channels are
consecutively numbered from 6 to 11, starting at terminal X531 (see function diagram 9627
in the SINAMICS S120/S150 Lists Manual).
Example of 8 temperature channels:
2x2 conductors at terminal X531: p4108[0] = 1 ≙ sensor 1 is at channel 0 and sensor 2 is at
channel 6
2x2 wires at terminal X532: p4108[1] = 1 ≙ sensor 1 is at channel 1 and sensor 2 is at
channel 7
1x3 wires at terminal X533: p4108[2] = 2 ≙ sensor 1 is at channel 2
1x3 conductor is at terminal X534: p4108[3] = 2 ≙ sensor 1 is at channel 3
1x4 conductor is at terminal X535: p4108[4] = 3 ≙ sensor 1 is at channel 4
1x2 conductor is at terminal X536: p4108[5] = 0 ≙ sensor 1 is at channel 5

Table of Contents

Other manuals for Siemens SINAMICS S120

Related product manuals