Vector control
5.1 Technological application
Drive functions
208 Function Manual, 11/2017, 6SL3097-4AB00-0BP5
5.1
Technological application
Using parameter p0500, you can influence the calculation of open-loop control and closed-
loop control parameters. The default setting helps you find suitable values for standard
applications.
You can make preassignments for the following technological applications:
Value p0500
Application
0
Standard drive (VECTOR)
1
Pumps and fans
2
Encoderless control down to f = 0 (passive loads)
4
Dynamic respons
e in the field weakening range
5
Starting with high breakaway torque
6
High load moment of inertia (e.g. centrifuges)
An overview of the influenced parameters and the set values is provided in the "SINAMICS
S120/S150 List Manual".
Calculation
You call the calculation of the parameters, which influence the technological application, as
follows:
When exiting quick commissioning with p3900 > 0
When automatically calculating the motor/closed-loop control parameters with
p0340 = 1, 3, 5 (for p0500 = 6: p0340 = 1, 3, 4)
When calculating the technology-dependent parameters with p0578 = 1