Safety Integrated Basic Functions
10.2 General information
Drive functions
674 Function Manual, 11/2017, 6SL3097-4AB00-0BP5
10.2.3
Control possibilities
The following options for controlling Safety Integrated functions are available:
Table 10- 1 Controlling the Safety Integrated functions
Control via:
Basic
Extended
Advanced
Terminals
(on the Control Unit and
Motor/Power Module)
x - -
PROFIsafe based on
PROFIBUS or PROFINET
x x x
TM54F
x
x
x
Control without selection
-
SLS, SDI
-
Onboard F-DI/F-DO
(CU310-2)
x
1)
x x
1)
Only the F-DI 0 can be used for the control. The F-DO is not available.
Note
PROFIsafe or TM54F
Using a Control Unit, control is possible either via PROFIsafe o
r TM54F. Mixed operation is
not permissible.
10.2.4
Parameter, Checksum, Version, Password
Properties of Safety Integrated parameters
The following applies to Safety Integrated parameters:
They are kept separate for each monitoring channel.
During startup, checksum calculations (Cyclic Redundancy Check, CRC) are performed
on the safety parameter data and checked. The display parameters are not contained in
the CRC.
Data storage: The parameters are stored on the non-volatile memory card.