Communication 
  11.3 Communication via PROFINET IO 
Drive functions 
Function Manual, 11/2017, 6SL3097-4AB00-0BP5 
805 
Cyclic communication using PROFINET IO with IRT or using RT is possible on all drive units 
equipped with a PROFINET interface. This means that error-free communication using other 
standard protocols is guaranteed within the same network. 
 
Note 
PROFINET for drive technology is standardized and described in the following document: 
 
PROFIBUS profile PROFIdrive 
- Profile Drive Technology  
.1, May 2006  
PROFIBUS User Organization e. V.
 
-und-Neu-Straße 7  
-76131 Karlsruhe 
http://www.profibus.com)  
Order no. 3.172, spec. Section 6
 
  IEC 61800-7 
 
-2 DP with inserted CBE20, the cyclic PZD channel for PROFIBUS DP is 
deactivated. When setting parameter p8839
 = 1, the PZD channel can be reactivated (see 
Parallel operation of communication interfaces (Page 749)"). 
 
Real-time (RT) and isochronous real-time (IRT) communication 
Real-time communication  
When communication takes place via TCP/IP, the resultant transmission times may be too 
long and not defined to meet the production automation requirements. When communicating 
time-critical IO user data, PROFINET IO therefore uses its own real-time channel, rather 
than TCP/IP.  
Real time means that a system processes external events over a defined period. 
Determinism means that a system will react in a predictable ("deterministic") manner. 
With PROFINET IO with IRT, it is possible to precisely determine (predict) transmission 
times. 
PROFINET IO with RT (Real Time)  
Real-time data is treated with a higher priority than TCP(UDP)/IP data. Transmission of time-
critical data takes place at guaranteed time intervals. RT communication provides the basis 
for data exchange with PROFINET IO.