Vector control 
  5.9 Vdc control 
Drive functions 
Function Manual, 11/2017, 6SL3097-4AB00-0BP5 
241 
 
Figure 5-16  Switching the V
dc_max
 control on/off 
The switch-on level for V
dc_max
-control (r1242) is calculated as follows:  
●  When the function for automatically detecting the switch-on level is switched off (p1254 = 
0) 
r1242 = 1.15 x p0210 (device connection voltage, DC link) 
●  When the function for automatically detecting the switch-on level is switched on (p1254 = 
1) 
r1242 = V
dc_max
 - 50 V (V
dc_max
: Overvoltage threshold of the Motor Module) 
If several Motor Modules are supplied from a non-regenerative infeed unit (e.g. a Basic Line 
Module), or for power failure or overload (for SLM/ALM), the V
dc_max
 control may only be 
activated for a Motor Module whose drive should have a high moment of inertia.  
For the other Motor Modules this function must be disabled or monitoring must be set.  
If the V
dc_max
control is active for several Motor Modules, then for an unfavorable 
parameterization, the controllers can mutually influence one another negatively. The drives 
can become unstable, individual drives can unintentionally accelerate.