Basic functions
7.7 dv/dt filter plus Voltage Peak Limiter
Drive functions
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
329
NOTICE
Damage to the du/dt filter by exceeding the maximum pulse frequency
Inadmissibly high pulse frequencies can damage the du/dt filter.
Do not exceed maximum permissible pulse frequency.
Commissioning
The dv/dt filter must be activated when commissioning the system (p0230 = 2).