Basic functions
7.8 dv/dt filter compact plus Voltage Peak Limiter
Drive functions
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
331
Restrictions
The following restrictions must be taken into account when a dv/dt filter is used:
The output frequency is limited to a maximum of 150 Hz.
Maximum permissible motor cable lengths:
Shielded cables: Max. 100 m
Unshielded cables: Max. 150 m
Further restrictions are contained in the following device manuals:
SINAMICS S120 AC Drive
SINAMICS S120 air-cooled chassis power units
SINAMICS S120 chassis power units, liquid-cooled
Commissioning
During commissioning, you must activate the dv/dt filter with p0230 = 2.