EasyManua.ls Logo

Siemens SINAMICS S120 - Page 34

Siemens SINAMICS S120
1094 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Infeed
2.1 Active Infeed
Drive functions
34 Function Manual, 11/2017, 6SL3097-4AB00-0BP5
Operating mode of Active Infeed closed-loop control for Active Line Modules chassis.
Active Line Modules chassis only function in Active Mode.
In the Active Mode, the DC link voltage is regulated to a variable setpoint (p3510) which
results in a sinusoidal line current (cos φ = 1).
The DC link voltage setpoint (p3510) is preset depending on the supply voltage (p0210)
using the equation p3510 = 1.5 · p0210.
Commissioning
The device supply voltage (p0210) must be parameterized during commissioning. The
necessary line filter (p0220) is preset.
When it is first switched on with a new/modified network, an automatic controller setting
should be implemented using the line / DC link identification routine (p3410).
While the identification routine is running, it is not permissible that other loads are switched-
in/switched-out.
Note
In a supply system without regenerative feedback capability (e.g. generators), regenerative
operation must be inhibited via the binector input p3533.
The DC link voltage (p3510) can be set within the following limits:
Upper limit:
Maximum DC link voltage (p0280)
Product of the supply voltage (p0210) and step-up factor (max. p3508 = 2.00)
Lower limit: Supply voltage (p0210) multiplied by 1.42
For the DC link voltage, the following values apply for chassis units (p0280):
Device voltage
Default setting
Minimum
Maximum
380 ... 480 V
750 V
50 V
785 V
500 ... 690 V
0.875 · p0210 + 502 V
50 V
1130 V
NOTICE
Overheating of the components
An excessively high step-up factor for Active Line Modules Chassis can overheat and
destroy components.
Set the step-up factor to a maximum value of 2.00.

Table of Contents

Other manuals for Siemens SINAMICS S120

Related product manuals